DS8100A REFERENCE MANUAL
46
4
Output 3 has different electrical features. It is a bi-directional solid state relay with built-in
current limit protection.
Output 3
Maximum Voltage ± 100 V (Vext only)
Collector Current (pulse) 300 mA Max. at 25°C (Ambient temperature)
240 mA Max. at 50°C (Ambient temperature)
Collector Current (continuous) 200 mA Max. at 25°C (Ambient temperature)
150 mA Max. at 50°C (Ambient temperature)
R on
R off
6 – 15 Ω
> 500 Ω
Off-State Leakage Current < 1 µA
Maximum Power Dissipation 550 mW at 50°C (Ambient temperature)
Pin Name Function
8 O1+ Configurable digital output 1 – positive pin
22 O1- Configurable digital output 1 – negative pin
11 O2+ Configurable digital output 2 – positive pin
12 O2- Configurable digital output 2 – negative pin
16 O3A Configurable digital output 3 – polarity insensitive
17 O3B Configurable digital output 3 – polarity insensitive
The function of each output can be defined by the user (No Read, Right, Wrong, etc.). Refer to
the Genius™ Help On-Line for further details.
The output signals are fully programmable being determined by the configured
Activation/Deactivation events, Deactivation Timeout or a combination of the two.
By default, Output 1 is associated with the Complete Read event, which activates when all
the selected codes are correctly decoded, and Output 2 is associated with the No Read
event, which activates when the code signaled by the external trigger/PS is not decoded.
Output 3 can be assigned to the same events and it has the advantage of being polarity
insensitive. By default it is not assigned to any event.
DS8100
USER INTERFACE
Vext
30 Vdc max
+
-
Figure 58 – Output 1 and Output 2 Interface
When the load is powered by an external power supply, the voltage must be less than 30 V.